> Services > APC > APC UPS Service

APC UPS Service

The APC UPS service provides basic and advanced APC UPS battery information.

Service Type

SNMP

Instances on a Device

1

Supported Systems/Applications

Any PowerNet-MIB Compliant Device from APC

Device Class

Server - Generic, Other, Printer, Scanner/Camera, Switch/Router, and Server - Windows.

Monitored By

Windows Probes

Scan Interval

15 minutes

OID/Calculation

Metric Name

OID/Calculation

Description

Status

1.3.6.1.4.1.318.1.1.1.2.1.1

The status of the UPS battery. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored:

  • unknown(1) translates to Warning,
  • batteryNormal(2) translates to Normal,
  • batteryLow(3) translates to Failed.

Time On

1.3.6.1.4.1.318.1.1.1.2.1.2

The elapsed time since the UPS has switched to battery power.

Last Replaced

1.3.6.1.4.1.318.1.1.1.2.1.3

The date when the UPS system's batteries were last replaced, in mm/dd/yy format. For Smart-UPS models, this value is originally set in the factory. When the UPS batteries are replaced, this value should be reset by the administrator.

Capacity

1.3.6.1.4.1.318.1.1.1.2.2.1

The remaining battery capacity expressed as a percentage.

Temperature

1.3.6.1.4.1.318.1.1.1.2.2.2

The current internal UPS temperature, expressed in degrees Celsius.

Time Remaining

1.3.6.1.4.1.318.1.1.1.2.2.3

The run time remaining before battery exhaustion.

Replace Indicator

1.3.6.1.4.1.318.1.1.1.2.2.4

Indicates if the UPS batteries need to be replaced:

  • noBatteryNeedsReplacing(1) translates to Normal,
  • batteryNeedsReplacing(2) translates to Failed.