> Services > APC > APC UPS – Humidity Service

APC UPS – Humidity Service

The APC UPS - Humidity services monitors the status and reported humidity of the specified environment sensor.

Service Type

SNMP

Instances on a Device

1

Supported Systems/Applications

Any APC UPS device that supports the PowerNet392 SNMP MIB, and has an attached environment sensor that reports humidity readings.

Device Class

Other

Monitored By

Windows Probe
Scan Interval 5 minutes
Environment Sensor Enter the name of the monitored environment sensor. To find out the name of the environment sensor attached to the UPS, query the UPS device with the .1.3.6.1.4.1.318.1.1.10.2.3.2.1.2 SNMP OID. The default name is Int Sensor.

OID/Calculation

Metric Name

OID/Calculation

Description

Humidity 1.3.6.1.4.1.318.1.1.10.2.3.2.1.6 The humidity reading .
Sensor Status 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 Monitors the status of the humidity sensor.
Sensor Status Description 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 Displays the current status of the humidity sensor. Two values can be returned: Connected or Disconnected.