> Services > NetBotz > NetBotz Airflow Service

NetBotz Airflow Service

The NetBotz Airflow service monitors the airflow reading and airflow sensor status of the specified temperature sensor.

This service cannot use Self-Healing.

Service Type

SNMP

Instances on a Device

68

Supported Systems/Applications

Any NetBotz device that has an attached airflow sensor.

Device Class

Other

Monitored By

Windows Probe
Scan Interval 5 minutes
Airflow Sensor To determine the name of the airflow sensors attached to the NetBotz device, query the NetBotz device with the 1.3.6.1.4.1.5528.100.4.1.5.1.1 SNMP OID.The default name is nbHawkEnc_0_AFLW.

OID/Calculation

Metric Name

OID/Calculation

Description

Airflow 1.3.6.1.4.1.5528.100.4.1.5.1.8  
Sensor Status 1.3.6.1.4.1.5528.100.4.1.5.1.3 This status is either Connected or Disconnected. The service reports a Failed Status if the sensor reports Disconnected.
Sensor Status Description 1.3.6.1.4.1.5528.100.4.1.5.1.3