> Services > NetBotz > NetBotz Dewpoint Service

NetBotz Dewpoint Service

The NetBotz Dewpoint service monitors the dew point reading, by default in degrees Celsius, and sensor status of the specified dewpoint sensor.

This service cannot use Self-Healing.

Service Type

SNMP

Instances on a Device

68

Supported Systems/Applications

Any NetBotz device that has an attached dewpoint sensor

Device Class

Other

Monitored By

Windows Probe
Scan Interval 5 minutes
Dewpoint Sensor To determine the name of the dewpoint sensors attached to the NetBotz device, query the NetBotz device with the 1.3.6.1.4.1.5528.100.4.1.3.1.1 SNMP OID. The default name is nbHawkEnc_0_DEW.

OID/Calculation

Metric Name

OID/Calculation

Description

Dewpoint 1.3.6.1.4.1.5528.100.4.1.3.1.8 The dew point temperature measured in degrees Celsius.
Dewpoint 1.3.6.1.4.1.5528.100.4.1.3.1.9 The dew point temperature measured in degrees Fahrenheit.
Sensor Status 1.3.6.1.4.1.5528.100.4.1.3.1.3 This status is either Connected or Disconnected. The service reports a Failed Status if the sensor reports Disconnected.
Sensor Status Description 1.3.6.1.4.1.5528.100.4.1.3.1.3