> Services > NetBotz > NetBotz Door Switch Service

NetBotz Door Switch Service

The NetBotz Door Switch service monitors whether or not the door switch is open or closed, and the status of the door sensor.

This service cannot use Self-Healing.

Service Type

SNMP

Instances on a Device

68

Supported Systems/Applications

Any NetBotz device that has an attached door switch

Device Class

Other

Monitored By

Windows Probe
Scan Interval 5 minutes
Door Switch To determine the name of the door switches attached to the NetBotz device, query the NetBotz device with the .1.3.6.1.4.1.5528.100.4.2.2.1.1 SNMP OID. Default name is DOOR.

OID/Calculation

Metric Name

OID/Calculation

Description

Door Switch Status 1.3.6.1.4.1.5528.100.4.2.2.1.2

An integer value representing whether or not the door switch is connected - the door is closed - or disconnected - the door is open. The service transitions to a Failed state if the door switch reports a disconnected status.

Door Switch Status Description 1.3.6.1.4.1.5528.100.4.2.2.1.2

Reports either Connected or Disconnected.

Sensor Status 1.3.6.1.4.1.5528.100.4.2.2.1.3

The health status of the sensor:

  • 0: Normal
  • 1: Info
  • 2: Warning
  • 3: Error 4:Critical
  • 5: Failure

This status is mapped as:

  • Normal: 0
  • Warning: 1,2
  • Failed: 3,4,5
Sensor Status Description 1.3.6.1.4.1.5528.100.4.2.2.1.3

A description of the health status of the sensor.